I have skills in circuit design, PCB layout, embedded systems programming, power electronics, and proficiency in simulation software like MATLAB and SPICE. Additionally, I am experienced in troubleshooting and testing electrical systems.
I have skills in circuit design, PCB layout, embedded systems programming, power electronics, and proficiency in simulation software like MATLAB and SPICE. Additionally, I am experienced in troubleshooting and testing electrical systems.
The knee point voltage of a current transformer (CT) can be calculated using the formula:
[ V_k = frac{I_s times R}{sqrt{3}} ]
where ( V_k ) is the knee point voltage, ( I_s ) is the saturation current of the CT, and ( R ) is the burden resistance connected to the CT.
To identify the ammeter and voltmeter, connect the wires to the 220 V supply.
1. Connect two wires to the voltmeter. If it shows a reading, it is the voltmeter.
2. Connect the remaining two wires to the ammeter. If it shows a reading, it is the ammeter.
The device that shows a reading when connected across the supply is the voltmeter, and the one that shows a reading when connected in series is the ammeter.
The setting of a thermal overload relay is adjusted based on the full-load current (FLC) of the motor it protects. To calculate the setting, use the formula:
Setting (A) = FLC x 0.8 to 1.1 (depending on the motor's service factor).
Adjust the relay to the calculated value to ensure proper protection.
Opening the secondary terminal of a current transformer can cause a high voltage to develop across the terminals, which can damage the transformer and pose a safety hazard.
1. Check power supply: Ensure the motor is receiving the correct voltage and current.
2. Inspect connections: Look for loose or damaged wiring and connectors.
3. Test the controller: Verify that the controller is functioning properly and check for error codes.
4. Measure motor resistance: Use a multimeter to check the motor windings for continuity and shorts.
5. Check for mechanical obstructions: Ensure the motor shaft is not blocked or jammed.
6. Test the motor: If possible, connect the motor directly to a power source to see if it runs.
7. Review control signals: Check if the controller is sending the correct signals to the motor.
First, check the power supply switch position then check connections properly in switch-off condition. Smell and touch components whether heated or not. After that replace the motor to identify the fault.
* 1st check the power supply switch whether on or off
* then Check the all wiring connections may be wire disconnected or there is any loose connection(OFF the switch).
* smell the component whether it is heated or not and touch to experiance the heat(OFF the switch).
* replace the controller/motor with new one to detect fault present in which part.
The electrical power (MW) output of an AC generator varies with the steam input to a steam turbine by adjusting the turbine's steam flow. Increasing steam input raises the turbine's rotational speed, which in turn increases the generator's output power. Conversely, reducing steam input decreases the turbine speed and lowers the power output. The relationship is generally proportional, as long as the generator operates within its design limits.
To calculate the size of copper and aluminum wire, use the following formula:
1. **Determine the current (I)** in amperes that the wire will carry.
2. **Select the allowable voltage drop (Vd)**, typically 2-5% of the supply voltage.
3. **Use the formula:**
[
A = frac{(2 times L times I times R)}{Vd}
]
Where:
- (A) = cross-sectional area in mm²
- (L) = one-way length of the wire in meters
- (R) = resistivity of the material (for copper, approximately 0.0175 ohm·mm²/m; for aluminum, approximately 0.0282 ohm·mm²/m)
4. **Choose the wire gauge** based on the calculated area, referring to standard wire gauge charts for copper and aluminum.
To wire a 20 HP motor, follow these steps:
1. **Select the Right Cable**: Use appropriate gauge wire based on the motor's voltage and distance from the power source.
2. **Install a Motor Starter**: Use a motor starter with overload protection suitable for a 20 HP motor.
3. **Connect Power Supply**: Connect the three-phase power supply to the motor starter input terminals.
4. **Connect Motor Leads**: Connect the motor leads (U, V, W) to the output terminals of the motor starter.
5. **Ground the Motor**: Ensure the motor is properly grounded to prevent electrical hazards.
6. **Control Circuit**: Wire the control circuit to the starter, including start/stop buttons.
7. **Check Connections**: Verify all connections are secure and correct.
8. **Test the Motor**: Power on the system and test the motor for proper operation.
Always follow local electrical codes and safety standards.
To calculate the GD² (Moment of Inertia) of high tension (HT) motors, use the formula:
[ GD² = frac{(P times 60)}{(2 pi N)} ]
Where:
- ( P ) = Power in watts
- ( N ) = Speed in RPM
Ensure to convert the power to the appropriate units if necessary.
Wet bulb temperature is the lowest temperature that can be achieved by evaporating water into the air, while dry bulb temperature is the air temperature measured by a regular thermometer. We use these temperatures in air conditioning to assess humidity levels and determine the efficiency of cooling systems.
A static device is one that does not have moving parts and operates based on electromagnetic principles, such as a transformer. A mechanical device, on the other hand, involves moving parts and mechanical motion. Yes, a transformer is a static device.
A consistency transmitter is a device used in industrial processes to measure the concentration or consistency of a fluid, typically in applications like pulp and paper, food and beverage, or chemical processing. It works by using sensors to detect the properties of the fluid, such as its density or viscosity, and then converts this information into an electrical signal that can be transmitted to a control system for monitoring and control purposes.
To calibrate a transmitter for the range of -100 to 300 mmwc, you can use a dual-range calibration approach. Set the transmitter to measure negative pressure (from -100 mmwc to 0 mmwc) using a reference vacuum source, and then calibrate it for positive pressure (from 0 mmwc to 300 mmwc) using a pressure source. Ensure that the transmitter is capable of handling both negative and positive ranges, and adjust the zero and span settings accordingly during calibration.
No, the rated capacity of the transformer cannot be increased from 20 MVA to 25 MVA simply by changing the cooling method from ONAN to ONAF. The transformer's capacity is primarily determined by its design and insulation, not just the cooling method.
A universal motor works on both AC and DC because its design allows the direction of current in the armature and field windings to change with the supply voltage, enabling it to operate efficiently on either type of current.
The healthy specific gravity of a lead-acid battery used in DG sets is typically between 1.265 and 1.300.
AVR (Automatic Voltage Regulator) is connected to the generator in a power plant.
NGR (Neutral Grounding Resistor) is required for an 11kV generator in a power plant to limit the fault current during a ground fault, protect the generator and associated equipment from damage, and ensure safe operation by maintaining system stability.
Yes, I believe I am fit for this job because I have the necessary skills, experience, and passion for electrical design engineering.
The Design Engineer – Electrical category on takluu.com is tailored for professionals and aspirants aiming to excel in electrical design roles. Electrical design engineers are responsible for planning, developing, and validating electrical systems for various applications, including power distribution, control systems, and electronics.
This section covers essential topics such as electrical circuit design, schematic diagrams, CAD software (like AutoCAD Electrical), wiring layouts, load calculations, and compliance with standards like IEC and NEC. You’ll also find questions related to design optimization, troubleshooting, protective devices, and safety protocols.
Interview questions often explore practical scenarios, for example:
-
“How do you approach designing a power distribution system?”
-
“Explain the use of AutoCAD Electrical in schematic design.”
-
“What factors do you consider for electrical load calculations?”
Our content presents complex design concepts in a clear and concise manner, supported by real-world examples and best practices. Whether you are fresh in the field or an experienced engineer, this category helps you prepare confidently for technical interviews and project discussions.
At Takluu, we keep this category updated with the latest tools, software advancements, and industry trends, ensuring you stay current and competitive in the electrical design domain.